Copper busbar current ratings by cross-section, plus the derating factors that decide whether those numbers survive in your enclosure.
| Cross-section (mm) | Area (mm²) | DC current (A) | AC 60 Hz (A) |
|---|---|---|---|
| 10 × 3 | 30 | ~150 | ~150 |
| 15 × 3 | 45 | ~200 | ~200 |
| 20 × 3 | 60 | ~250 | ~250 |
| 25 × 3 | 75 | ~300 | ~295 |
| 30 × 5 | 150 | ~450 | ~440 |
| 40 × 5 | 200 | ~550 | ~535 |
| 50 × 5 | 250 | ~650 | ~630 |
| 60 × 6 | 360 | ~800 | ~770 |
| 80 × 6 | 480 | ~1000 | ~960 |
| 100 × 6 | 600 | ~1150 | ~1100 |
| Factor | Effect | Typical derate |
|---|---|---|
| Ambient temperature | Higher ambient raises conductor temperature | −1% per °C above 40 °C |
| Bundled bars | Adjacent conductors heat each other | −10 to −20% depending on spacing |
| Enclosed / still air | Reduced convection | −10 to −25% |
| Altitude | Thinner air cools less effectively | −1% per 200 m above 1000 m |
| AC frequency | Skin and proximity effect push current to surfaces | Material above ~1 kHz; consult us |
| Pulsed current | Thermal mass absorbs short pulses | Can allow higher peaks than continuous |
Send the current profile, voltage class and installation conditions — we will size the busbar and document the calculation with your quotation.
Send the current profile, voltage class and installation conditions — we will size the busbar and document the calculation.